CSE vs. UL Strobe Results
- 
                
UL's threshold visibility test - Early evening residential setting with television and two 100W lights
- 
                    
AWAKE subjects who had their eyes closed required more light to alert than SLEEPING SUBJECTS
 
 - 
                    
 
| 
                   Strobe Intensities  | 
                
                   110 cd  | 
                
                   75 cd  | 
                
                   40 cd  | 
                
                   10 cd  | 
                
                   2 cd  | 
                
                   0.75 cd  | 
                
                   0.1 cd  | 
              
| 
                   UL Detection of Strobe Awake with Eyes Closed  | 
                
                   100%  | 
                
                   82%  | 
                
                   0%  | 
                
                   0%  | 
                
                   0%  | 
                
                   0%  | 
                
                   0%  | 
              
| 
                   UL Sleep Tests (adults w/o medication)  | 
                
                   100%  | 
                
                   95%  | 
                
                   95%  | 
                
                   90%  | 
                
                   77%  | 
                
                   63%  | 
                
                   50%  | 
              
| 
                   CSE Sleep Tests (deaf)  | 
                
                   57%  | 
                
                   N/A  | 
                
                   N/A  | 
                
                   N/A  | 
                
                   N/A  | 
                
                   N/A  | 
                
                   N/A  |